|
One of the main tasks is the installation of the vent
stack, which is included with all units.
The vent kits included in the shipping carton are
sufficient for installation in most single story
buildings. If more is needed they are normally easy to
find. All vent pipes are thinwall PVC.
The drawing at left illustrates some of the more common
vent stack configurations for self-contained system
installations.
-
Electric units with 2" stacks should have the minimum
number of bends, should use 45° elbows where possible,
and should not have bends totaling more than 360°.
- 3" SpaceSaver/Ecolet
Mobile vents and especially 4" Non-Electric vent stacks
should be installed as straight as possible. If 45°
elbows are needed in a 4" vent stack then a 12 Volt fan
should be included in the installation to assist
airflow.
-
Merging a Sun-Mar vent with other existing vents risks
interference and is not advised.
-
The diffuser included with all units is a simple but
effective device originally patented by Sun-Mar
principals to aid updraft, resist winter freeze-up, and
protect the vent from downdraft and weather.
-
As shown in the drawings they should be installed 2-3
feet above the peak of the roof for best performance.
This prevents downdraft.
-
Vent joints within the bathroom should be siliconed,
vent joints outside should be glued with CPVC glue.
-
It is very important that self-contained model vent
systems do not contain ANY horizontal runs or downward
slopes on the pipe.
-
See the
Winter Use section for additional tips on protecting
your vent stack in the winter
Detailed Vent Stack Installation Instructions
Electric Unit (2" and 3") Piping Installation
Piping can be installed up the inside wall; through the
wall at a slight angle and up the outside wall. The choice
depends on ease of installation, visibility, and
(especially if the toilet is to be used consistently
through a cold winter), the necessity of insulating all
exposed vent pipe.
Piping and fittings are of standard 2” PVC thin wall
tubing. Additional pipe or fittings are easily available
should you need them, from a building supply dealer. If
you cannot find them near your location, they are
available in 30” lengths directly through us.
i) Minimize the number of sharp angles as each reduces
vent efficiency. If it is
necessary to have angles in the vent pipe, it is
recommended that 45 degree angles are used whenever
possible. (90 degree elbows may be used as long as no
horizontal vent results - pipe may be bracketed at a
slight upwards angle to prevent this)
ii) Do not lead the vent pipe downward or horizontally at
any point. This may lead to the vent pipe being blocked by
condensate which would cause a urine smell in your
bathroom.
iii) All connectors in the vent pipe should be sealed. Use
silicone for the connection of the vent stack to the
toilet in case the toilet has to be moved or you have to
access the fan. PVC cement may be used in the rest of the
stack installation if desired.
iv) All exposed vent pipe should be insulated with the
foam insulation supplied with the toilet. This is
especially important for winter or residential use.
Non-Electric Unit (4") Piping Installation
Piping can be installed up the inside wall; through the
wall at a slight angle and up the outside wall (with this
configuration a 12 volt fan is necessary). The choice
depends on ease of installation, visibility, and
(especially if the toilet is to be used consistently
through a cold winter), the necessity of insulating all
exposed vent pipe.
Piping and fittings are of standard 4” PVC thin wall
tubing. Additional pipe or fittings are easily available
should you need them, from a building supply dealer. If
you cannot find them near your location, they are
available in 30” lengths directly through us.
i) The vent stack should be installed as near to vertical
as possible.
ii) Silicone caulking should be used for the connection of
the vent stack to the toilet because at some time the
toilet may have to be moved or your may wish to install a
12 volt fan in the vent stack.
iii) The Sun-Mar 12 Volt fan is fitted inside a 10” length
of 4” vent pipe for easy installation, should it be
needed. It is installed by either cutting out a section of
the vent immediately above the composting unit, or by
raising the vent stack off of the composting unit and
inserting the fan section. The fan can be used with a
solar panel and 12 volt battery, or by purchasing a 12
volt adapter
from your local hardware store and simply plugging it into
the wall.
iv) If a 12 Volt fan is installed it should operate
continuously, since otherwise it forms a partial blockage
in the vent stack. To install, you can either use PVC
connectors or a rubberized connector.
v) All connectors in the vent pipe should be sealed.
Leading the Vent Through The Roof (All Units)
As shown in the installation, the vent stack should end
about 20” above the peak of the roof so that it is less
subject to downdraft. Where the piping is taken through
the roof, the roof flashing provided may be used to seal
the installation or if a new roof is being installed, the
roof flashing should be laid underneath the new roofing
material. DO NOT install horizontal sections of vent pipe
to avoid leading the vent through the roof.
The Diffuser (All Units)
The diffuser provided with the unit is a simple device to
be installed at the top of the vent stack with the larger
pipe protruding above the smaller. The diffuser design
encourages updraft, and discourages wind and weather from
going down the vent stack. Unlike wind turbines, diffusers
are less likely to freeze up in winter, and are more
effective in calm weather.
|

The Diagram above shows electric Excel, Compact, or
SpaceSaver configurations. The diagram at right shows
possible Excel-NE configurations - the 45 degree
configuration is dotted because it can only be installed
this way when a 12 Volt Fan is in the stack. |